21.2.10.4 Settings
Table 908: IOMIN Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - On Binary input/output module in operation
(On) or not (Off)
DebounceTime 0.001 - 0.020 s 0.001 0.001 Debounce time for binary inputs
OscBlock 1 - 40 Hz 1 40 Oscillation block limit
OscRelease 1 - 30 Hz 1 30 Oscillation release limit
21.2.10.5 Monitored data
Table 909: IOMIN Monitored data
Name Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok
1=Error
- Binary input part of IOM
module status
Table 910: IOMOUT Monitored data
Name
Type Values (Range) Unit Description
BO1VALUE BOOLEAN 1=1
0=0
- Binary output 1 value
BO1FORCE BOOLEAN 0=Normal
1=Forced
- Binary output 1 force
BO1 BOOLEAN 0=Normal
1=Forced
2=Blocked
-
Binary output 1 status
BO2VALUE BOOLEAN 1=1
0=0
- Binary output 2 value
BO2FORCE BOOLEAN 0=Normal
1=Forced
- Binary output 2 force
BO2 BOOLEAN 0=Normal
1=Forced
2=Blocked
-
Binary output 2 status
BO3VALUE BOOLEAN 1=1
0=0
- Binary output 3 value
BO3FORCE BOOLEAN 0=Normal
1=Forced
- Binary output 3 force
BO3 BOOLEAN 0=Normal
1=Forced
2=Blocked
-
Binary output 3 status
BO4VALUE BOOLEAN 1=1
0=0
- Binary output 4 value
BO4FORCE BOOLEAN 0=Normal
1=Forced
- Binary output 4 force
BO4 BOOLEAN 0=Normal
1=Forced
2=Blocked
-
Binary output 4 status
Table continues on next page
1MRK502052-UEN B Section 21
IED hardware
1177