13.2.6 Monitored data
Table 353: FUFSPVC Monitored data
Name
Type Values (Range) Unit Description
3I0 REAL - A Magnitude of zero
sequence current
3I2 REAL - A Magnitude of negative
sequence current
3U0 REAL - kV Magnitude of zero
sequence voltage
3U2 REAL - kV Magnitude of negative
sequence voltage
13.2.7 Operation principle
13.2.7.1 Zero and negative sequence detection
The zero and negative sequence function continuously measures the currents and
voltages in all three phases and calculates, see figure
289:
the zero-sequence voltage 3U0
the zero-sequence current 3I0
the negative sequence current 3I2
the negative sequence voltage 3U2
The measured signals are compared with their respective set values 3U0> and 3I0<,
3U2> and 3I2<.
The function enable the internal signal FuseFailDetZeroSeq if the measured zero-
sequence voltage is higher than the set value 3U0> and the measured zero-sequence
current is below the set value 3I0<.
The function enable the internal signal FuseFailDetNegSeq if the measured negative
sequence voltage is higher than the set value 3U2> and the measured negative
sequence current is below the set value 3I2<.
A drop out delay of 100 ms for the measured zero-sequence and negative sequence
current will prevent a false fuse failure detection at un-equal breaker opening at the
two line ends.