EasyManua.ls Logo

ABB REG670 - Technical Data

ABB REG670
1298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
regulated DC/DC converter that provides full isolation between the terminal and the
external battery system.
Connection diagram
IEC08000476 V2 EN
Figure 523: PSM Connection diagram.
21.2.3.3 Technical data
Table 886: PSM - Power supply module
Quantity
Rated value Nominal range
Auxiliary DC voltage, EL (input) EL = (24-60) V
EL = (90-250) V
EL ±20%
EL ±20%
Power consumption 50 W typically -
Auxiliary DC power in-rush < 10 A during 0.1 s -
21.2.4 Local human-machine interface (Local HMI)
Refer to section "Local HMI" for information.
21.2.5 Transformer input module (TRM)
21.2.5.1 Introduction
The transformer input module is used to galvanically separate and adapt the secondary
currents and voltages generated by the measuring transformers. The module has
twelve inputs in different combinations of currents and voltage inputs. Either
protection class or metering class CT inputs are available.
Alternative connectors of Ring lug or Compression type can be ordered.
1MRK502052-UEN B Section 21
IED hardware
1151
Technical manual

Table of Contents

Other manuals for ABB REG670