EasyManua.ls Logo

ABB REG670 - Generic Communication Function for Double Point Indication DPGAPC

ABB REG670
1298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IPOS1 IPOS2 Name of displayed string Default string value
0 0 PosUndefined P00
1 0 Position1 P01
0 1 Position2 P10
1 1 PosBadState P11
14.7 Generic communication function for Double Point
indication DPGAPC
14.7.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Generic communication function for
Double Point indication
DPGAPC - -
14.7.2 Functionality
Generic communication function for Double Point indication DPGAPC function
block is used to send double indications to other systems, equipment or functions in
the substation through IEC 61850-8-1 or other communication protocols. It is
especially used in the interlocking station-wide logics.
14.7.3 Function block
IEC13000081 V1 EN
Figure 362: DPGAPC function block
14.7.4 Signals
Table 455: DPGAPC Input signals
Name
Type Default Description
OPEN BOOLEAN 0 Open indication
CLOSE BOOLEAN 0 Close indication
VALID BOOLEAN 0 Valid indication
Section 14 1MRK502052-UEN B
Control
768
Technical manual

Table of Contents

Other manuals for ABB REG670

Related product manuals