15.7.2.1 Function block
INDCOMBSPQT
SP_IN*
TIME*
BLOCKED*
SUBST*
INVALID*
TEST*
SP_OUT
IEC15000146.vsd
IEC15000146 V1 EN
Figure 388: INDCOMBSPQT function block
15.7.2.2 Signals
Table 549: INDCOMBSPQT Input signals
Name Type Default Description
SP_IN BOOLEAN 0 Single point indication
TIME GROUP
SIGNAL
0 Timestamp
BLOCKED BOOLEAN 0 Blocked for update
SUBST BOOLEAN 0 Substitued
INVALID BOOLEAN 0 Invalid value
TEST BOOLEAN 0 Testmode
Table 550: INDCOMBSPQT Output signals
Name
Type Description
SP_OUT BOOLEAN Single point indication
15.7.2.3 Technical data
Table 551: Number of INDCOMBSPQT instances
Logic block
Quantity with cycle time
3 ms 8 ms 100 ms
INDCOMBSPQT - 10 10
15.7.3 Single point input signal attributes converting function block
INDEXTSPQT
The value part of the single point input signal SI_IN is copied to SI_OUT output. The
time part of single point input is copied to the TIME output. The state bits in the
common part and the indication part of the input signal are copied to the corresponding
state output.
1MRK502052-UEN B Section 15
Logic
823
Technical manual