BI
AI (U), current measure
AI (U), voltage measure
BI
RL+
RL+
BI
BI
RL+
BI
(BI)
REG670
PE
EL
+
-
X61:14; I
A
sense
X61:15; I
B
sense
X61:12; U
A
sense
X61:13; U
B
sense
UA Out; X61:8
UB Out; X61:9
IA Out; X61:10
IB Out; X61:11
UA Out; X81:8
UB Out; X81:9
IA Out; X81:10
IB Out; X81:11
Block 220V; X61:1
Block 110V; X61:2
Block 48V; X61:3
Block Common; X61:4
Block 220V; X81:1
Block 110V; X81:2
Block 48V; X81:3
Block Common; X81:4
Blocked; X61:5
Saturation; X61:6
Common; X61:7
Blocked; X81:5
Saturation; X81:6
Common; X81:7
REX060
Injection unit
PE
Ready; X11:1
Common; X11:2
Fail; X11:3
X11:4
X11:5
Rotor
Exciter
source
RL-
BO
RL-
BO
X82:1; Inj
A
X82:4; Inj
B
X82:2; InjSh
B
X81:14; I
A
sense
X81:15; I
B
sense
X81:12; U
A
sense
X81:13; U
B
sense
X82:3; Inj
A
X82:5; Inj
B
X81:16; I
A
sense
X62:1; InjExt
A
X62:4; Inj
B
X62:2; InjExt
B
X62:3; Inj
A
X62:5; Inj
B
Rotor Module (RIM)
Stator Module (SIM)
Power Supply Module
R
Distribution
Transformer
Stator
X1:7; Rotor -
X1:1; Rotor +
Injection; X1:9
Ground; X1:10
REX061
Coupling Capacitor unit
PE
X1:2; Injection A
X1:4; Injection B
External A; X1:9
External B; X1:10
I sense A; X1:6
I sense B; X1:8
REX062
Shunt Resistor unit
PE
IEC11000017-1-en.vsd
IEC11000017 V1 EN
Figure 572: Example installation when REX062 unit is required
22.5 Technical data
22.5.1 Hardware
Table 947: REX060 Technical data
Specifications
Values
Case size 6U, 1/2 19”; 223.7 x 245 x 267 mm (W x D x H)
Weight 8.0 kg
Burden, binary inputs BI 220 V: burden 0.4 W
BI 110 V: burden 0.2 W
BI 48 V: burden 0.1 W
Burden, RIM injection
< 10 VA at 100 V external disturbance
Burden, SIM injection
< 10 VA at 12 V earth fault voltage
0 VA at > 10% of maximum earth fault voltage
Burden, SIM injection with REX062
< 1 VA at 24 V earth fault voltage
Burden, measuring transformer SIM
< 60 mVA at 24 V; 87 Hz
Burden, measuring transformer RIM
< 60 mVA at 50 V; 113 Hz
Installation category III
Pollution degree 2
Section 22 1MRK502052-UEN B
Injection equipment hardware
1232
Technical manual