Name of OUTx Type Description Value when
activated
Value when
deactivated
OUT8 BOOLEAN Output 8 128 0
OUT9 BOOLEAN Output 9 256 0
OUT10 BOOLEAN Output 10 512 0
OUT11 BOOLEAN Output 11 1024 0
OUT12 BOOLEAN Output 12 2048 0
OUT13 BOOLEAN Output 13 4096 0
OUT14 BOOLEAN Output 14 8192 0
OUT15 BOOLEAN Output 15 16384 0
OUT16 BOOLEAN Output 16 32768 0
The sum of the numbers in column “Value when activated” when all OUTx (1≤x≤16)
are active equals 65535. This is the highest integer that can be converted to boolean by
the ITBGAPC function block.
The operator position input (PSTO) determines the operator place. The integer
number that is communicated to the ITBGAPC can only be written to the block while
the PSTO is in position “Remote”. If PSTO is in position ”Off” or ”Local”, then no
changes are applied to the outputs.
15.13.7 Technical data
Table 602: Number of ITBGAPC instances
Function
Quantity with cycle time
3 ms 8 ms 100 ms
ITBGAPC 4 4 8
15.14 Pulse integrator TIGAPC
15.14.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Pulse integrator TIGAPC
15.14.2 Functionality
The integrator function TIGAPC integrates input pulses and compares the integrated
time with a settable time delay to operate. Moreover, the time delay to reset the output
is settable in this function.
Section 15 1MRK502052-UEN B
Logic
848
Technical manual