15.8 Extension logic package
When extra configurable logic blocks are required, an additional package can be
ordered.
Table 586: Number of instances in the extension logic package
Logic block Quantity with cycle time
3 ms 8 ms 100 ms
AND 40 40 100
GATE - - 49
INV 40 40 100
LLD - - 49
OR 40 40 100
PULSETIMER 5 5 49
SLGAPC 10 10 54
SRMEMORY - - 110
TIMERSET - - 49
VSGAPC 10 10 110
XOR - - 49
15.9 Fixed signals FXDSIGN
15.9.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Fixed signals FXDSIGN - -
15.9.2 Functionality
The Fixed signals function FXDSIGN generates nine pre-set (fixed) signals that can
be used in the configuration of an IED, either for forcing the unused inputs in other
function blocks to a certain level/value, or for creating certain logic. Boolean, integer,
floating point, string types of signals are available.
1MRK502052-UEN B Section 15
Logic
835
Technical manual