energy values are available as output signals and also as pulse outputs. Integration of
energy values can be controlled by inputs (STARTACC and STOPACC) and EnaAcc
setting and it can be reset to initial values with RSTACC input.
The maximum demand for active and reactive powers are calculated for the set time
interval tEnergy and these values are updated every minute through output channels.
The active and reactive maximum power demand values are calculated for both
forward and reverse direction and these values can be reset with RSTDMD input.
17.2.3 Function block
ETPMMTR
P*
Q*
STARTACC
STOPACC
RSTACC
RSTDMD
ACCINPRG
EAFPULSE
EARPULSE
ERFPULSE
ERRPULSE
EAFALM
EARALM
ERFALM
ERRALM
EAFACC
EARACC
ERFACC
ERRACC
MAXPAFD
MAXPARD
MAXPRFD
MAXPRRD
IEC14000019-1-en.vsd
IEC14000019 V1 EN
Figure 455: ETPMMTR function block
17.2.4 Signals
Table 715: ETPMMTR Input signals
Name
Type Default Description
P REAL 0 Measured active power
Q REAL 0 Measured reactive power
STARTACC BOOLEAN 0 Start to accumulate energy values
STOPACC BOOLEAN 0 Stop to accumulate energy values.
RSTACC BOOLEAN 0 Reset of accumulated enery reading
RSTDMD BOOLEAN 0 Reset of maximum demand reading
Table 716: ETPMMTR Output signals
Name
Type Description
ACCINPRG BOOLEAN Accumulation of energy values in progress
EAFPULSE BOOLEAN Accumulated forward active energy pulse
EARPULSE BOOLEAN Accumulated reverse active energy pulse
Table continues on next page
Section 17 1MRK502052-UEN B
Metering
986
Technical manual