18.6.13.3 Function block
IEC10000285-1-en.vsd
I103GENCMD
BLOCK ^CMD_OFF
^CMD_ON
IEC10000285 V1 EN
Figure 482: I103GENCMD function block
18.6.13.4 Signals
Table 772: I103GENCMD Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of command
Table 773: I103GENCMD Output signals
Name Type Description
CMD_OFF BOOLEAN Command output OFF
CMD_ON BOOLEAN Command output ON
18.6.13.5 Settings
Table 774: I103GENCMD Non group settings (basic)
Name
Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 1 Function type (1-255)
PulseLength 0.000 - 60.000 s 0.001 0.400 Pulse length
InfNo 1 - 255 - 1 1 Information number for command output
(1-255)
18.6.14 IED commands with position and select for IEC 60870-5-103
I103POSCMD
18.6.14.1 Functionality
I103POSCMD is a transceiver function that monitors activity on its input signals and
interprets any state transition into commands then sent over an established IEC
60870-5-103 link. Additionally, it listens for general interrogation (GI) requests and
replies to those with a GI response message with the current state of each connected
input.
Input POSITION is a double-indication signal, and it is GI enabled. This means that
any state transition, that is to ON, OFF, intermediate and faulty, is reported
spontaneously. However, the intermediate and faulty states may be suppressed by
Section 18 1MRK502052-UEN B
Station communication
1048
Technical manual