18.14 Security events on protocols SECALARM
18.14.1 Security alarm SECALARM
18.14.1.1 Signals
Table 812: SECALARM Output signals
Name Type Description
EVENTID INTEGER EventId of the generated security event
SEQNUMBER INTEGER Sequence number of the generated security event
18.14.1.2 Settings
Table 813: SECALARM Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - On Operation On/Off
18.15 Activity logging parameters ACTIVLOG
18.15.1 Activity logging ACTIVLOG
ACTIVLOG contains all settings for activity logging.
There can be 6 external log servers to send syslog events to. Each server can be
configured with IP address; IP port number and protocol format. The format can be
either syslog (RFC 5424) or Common Event Format (CEF) from ArcSight.
18.15.2 Settings
Table 814: ACTIVLOG Non group settings (basic)
Name
Values (Range) Unit Step Default Description
ExtLogSrv1Type Off
SYSLOG UDP/IP
SYSLOG TCP/IP
CEF TCP/IP
-
- Off External log server 1 type
ExtLogSrv1Port 1 - 65535 - 1 514 External log server 1 port number
ExtLogSrv1IP 0 - 18 IP
Address
1 127.0.0.1 External log server 1 IP-address
ExtLogSrv2Type Off
SYSLOG UDP/IP
SYSLOG TCP/IP
CEF TCP/IP
-
- Off External log server 2 type
Table continues on next page