15.6.6.1 Function block
PULSETIMER
INPUT OUT
IEC04000407-3-en.vsd
IEC04000407 V3 EN
Figure 381: PULSETIMER function block
15.6.6.2 Signals
Table 524: PULSETIMER Input signals
Name Type Default Description
INPUT BOOLEAN 0 Input to pulse timer
Table 525: PULSETIMER Output signals
Name Type Description
OUT BOOLEAN Output from pulse timer
15.6.6.3 Settings
Table 526: PULSETIMER Non group settings (basic)
Name
Values (Range) Unit Step Default Description
t 0.000 - 90000.000 s 0.001 0.010 Time delay of function
15.6.6.4 Technical data
Table 527: Number of PULSETIMER instances
Logic block
Quantity with cycle time Range or Value Accuracy
3 ms 8 ms 100 ms
PULSETIMER 10 10 20 (0.000–90000.000) s ±0.5% ±10 ms
15.6.7 Reset-set with memory function block RSMEMORY
The Reset-set with memory function block (RSMEMORY) is a flip-flop with memory
that can reset or set an output from two inputs respectively. Each RSMEMORY
function block has two outputs, where one is inverted. The memory setting controls if,
after a power interruption, the flip-flop resets or returns to the state it had before the
power interruption. For a Reset-Set flip-flop, RESET input has higher priority over
SET input.
1MRK502052-UEN B Section 15
Logic
815
Technical manual