Name Type Default Description
INPUT4 BOOLEAN 0 Binary signal input 4
INPUT5 BOOLEAN 0 Binary signal input 5
INPUT6 BOOLEAN 0 Binary signal input 6
INPUT7 BOOLEAN 0 Binary signal input 7
INPUT8 BOOLEAN 0 Binary signal input 8
RT_START BOOLEAN 0 Trig to set base of relative time
RT_START registers the positive transition (0->1) of a pulse and sets the time from
which relative time is derived. Relative time is assigned only to inputs where the
corresponding TypNo parameter is set to Relative. The maximum relative time and
unit conform to the IEC 60870-5-103 standard.
18.6.9.5 Settings
Table 762: I103USRDEF Non group settings (basic)
Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 5 Function type (1-255)
InfNo1 1 - 255 - 1 1 Information number for binary input 1
(1-255)
InfNo2 1 - 255 - 1 2 Information number for binary input 2
(1-255)
InfNo3 1 - 255 - 1 3 Information number for binary input 3
(1-255)
InfNo4 1 - 255 - 1 4 Information number for binary input 4
(1-255)
InfNo5 1 - 255 - 1 5 Information number for binary input 5
(1-255)
InfNo6 1 - 255 - 1 6 Information number for binary input 6
(1-255)
InfNo7 1 - 255 - 1 7 Information number for binary input 7
(1-255)
InfNo8 1 - 255 - 1 8 Information number for binary input 8
(1-255)
TypNo1 Absolute
Relative
- - Absolute Type identification (TYP)
TypNo2 Absolute
Relative
- - Absolute Type identification (TYP)
TypNo3 Absolute
Relative
- - Absolute Type identification (TYP)
TypNo4 Absolute
Relative
- - Absolute Type identification (TYP)
TypNo5 Absolute
Relative
- - Absolute Type identification (TYP)
TypNo6 Absolute
Relative
- - Absolute Type identification (TYP)
Table continues on next page
Section 18 1MRK502052-UEN B
Station communication
1042
Technical manual