EasyManua.ls Logo

ABB REG670 - Technical Data

ABB REG670
1298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
blocks with the text inside: 2nd Harmonic; Wave block and 5th Harmonic). If
there is less harmonic pollution. than allowed by the settings I2/I1Ratio, and I5/
I1Ratio, (then the outputs from the blocks 2nd harmonic and 5th harmonic is 0)
then it is assumed that a minor simultaneous internal fault must have occurred.
Only under these conditions a trip command is allowed (the signal TRIPRESL1
is = 1). The cross-block logic scheme is automatically applied under such
circumstances. (This means that the cross block signals from the other two phases
L2 and L3 is not activated to obtain a trip on the TRIPRESL1 output signal in
figure
39)
6. All start and blocking conditions are available as phase segregated as well as
common (that is three-phase) signals.
a>b
a
b
&
t
tAlarm Delay
IDALARM
a>b
a
b
a>b
a
b
IDL1 MAG
I Diff Alarm
I Diff Alarm
I Diff Alarm
IDL2 MAG
IDL3 MAG
en06000546.vsd
IEC06000546 V1 EN
Figure 43: Differential current alarm logic
6.1.8 Technical data
Table 48: T2WPDIF, T3WPDIF technical data
Function
Range or value Accuracy
Operating characteristic Adaptable ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir
Reset ratio > 90% -
Unrestrained differential current limit (100-5000)% of
IBase
on high voltage
winding
±1.0% of set value
Minimum pickup (5-60)% of IBase ±1.0% of Ir
Second harmonic blocking (5.0-100.0)% of fundamental
differential current
±1.0% of I
r
Note: fundamental
magnitude =
100% of I
r
Fifth harmonic blocking
(5.0-100.0)% of fundamental
differential current
±5.0% of I
r
Note: fundamental
magnitude =
100% of I
r
Table continues on next page
Section 6 1MRK502052-UEN B
Differential protection
140
Technical manual

Table of Contents

Other manuals for ABB REG670

Related product manuals