Figure 147: Block diagram of ZGVPDIS
7.10.7.1 Operation principle of zone 1
In general, the zone 1 must cover the generator winding, the cables or busbars and step
up transformer.
Under impedance functionality is provided as selective protection for the phase-to-
phase faults in zone 1. Hence the functionality of zone 1 includes only phase-to-phase
measuring loops.
Zone 1 functionality can be set to PP Loops or Off using the setting OpModeZ1.
Figure 148 shows the functionality of zone 1.