Figure 148: Block diagram of zone 1
The functionality included in zone 1:
• Comparator to detect, if the operating impedance has entered inside zone 1 offset
mho characteristic.
• All three phase-to-phase loops are implemented separately.
• Forward and reverse reach values are provided in percentage of impedance base
value at generator.
• Operate time delay is provided.
Comparator characteristics
The comparator consists of offset mho characteristics. Three individual comparators
are provided in the three phase-to-phase loops. The offset mho characteristic is as
shown in figure
149.