TRZ1
IEC11000297-3-en.vsd
<
<
<
BLOCK
BLKZ
U3P
I3P
STZ1
OpModeZ1
Z1Fwd
Z1Rev
Comparator
ZL1L2
OPModeZ1
Z1Fwd
Z1Rev
Comparator
ZL2L3
Comparator
ZL3L1
OpModeZ1
Z1Fwd
Z1Rev
1
³
ImpedanceAng
ImpedanceAng
ImpedanceAng
t
tZ1
IEC11000297 V3 EN
Figure 148: Block diagram of zone 1
The functionality included in zone 1:
Comparator to detect, if the operating impedance has entered inside zone 1 offset
mho characteristic.
All three phase-to-phase loops are implemented separately.
Forward and reverse reach values are provided in percentage of impedance base
value at generator.
Operate time delay is provided.
Comparator characteristics
The comparator consists of offset mho characteristics. Three individual comparators
are provided in the three phase-to-phase loops. The offset mho characteristic is as
shown in figure
149.
1MRK502052-UEN B Section 7
Impedance protection
325
Technical manual