Table 214: GUPPDUP Output signals
Name Type Description
TRIP BOOLEAN Common trip signal
TRIP1 BOOLEAN Trip of stage 1
TRIP2 BOOLEAN Trip of stage 2
START BOOLEAN Common start
START1 BOOLEAN Start of stage 1
START2 BOOLEAN Start of stage 2
P REAL Active Power in MW
PPERCENT REAL Active power in % of SBase
Q REAL Reactive power in MVAr
QPERCENT REAL Reactive power in % of SBase
8.10.5 Settings
Table 215: GUPPDUP Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
OpMode1 Off
UnderPower
- - UnderPower Operation mode for stage 1 Off / On
Power1 0.0 - 500.0 %SB 0.1 1.0 Stage 1 underpower setting in Angle1
direction in % of SBase
Angle1 -180.0 - 180.0 Deg 0.1 0.0 Characteristic angle for max power
senistivity stage 1
TripDelay1 0.01 - 6000.00 s 0.01 1.00 Trip delay for stage 1
DropDelay1 0.01 - 6000.00 s 0.01 0.06 Drop-off delay for stage 1
OpMode2 Off
UnderPower
- - UnderPower Operation mode for stage 2 Off / On
Power2 0.0 - 500.0 %SB 0.1 1.0 Power setting for stage 2 in % of SBase
Angle2 -180.0 - 180.0 Deg 0.1 0.0 Characteristic angle for max power
senistivity stage 2
TripDelay2 0.01 - 6000.00 s 0.01 1.00 Trip delay for stage 2
DropDelay2 0.01 - 6000.00 s 0.01 0.06 Drop-off delay for stage 2
Table 216: GUPPDUP Group settings (advanced)
Name
Values (Range) Unit Step Default Description
k 0.000 - 0.999 - 0.001 0.000 Low pass filter coefficient for power
measurement, P and Q
Hysteresis1 0.2 - 5.0 %SB 0.1 0.5 Absolute hysteresis of stage 1 in % SBase
Hysteresis2 0.2 - 5.0 %SB 0.1 0.5 Absolute hysteresis of stage 2 in % SBase
IAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
current error at 5% of Ir
Table continues on next page