15.14.3 Function block
TIGAPC
IN OUT
TIGAPC
IN OUT
IEC14000013-1-en.vsd
IEC14000013 V1 EN
Figure 403: TIGAPC function block
15.14.4 Signals
Table 603: TIGAPC Input signals
Name Type Default Description
IN BOOLEAN 0 Input to integrator
Table 604: TIGAPC Output signals
Name Type Description
OUT BOOLEAN Output from integrator
15.14.5 Settings
Table 605: TIGAPC Group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
tDelay 0.000 - 600.000 s 0.001 1.000 Time delay to operate
tReset 0.000 - 600.000 s 0.001 1.000 Time delay to reset
15.14.6 Operation principle
In the pulse integrator TIGAPC, the time during which the input is high is integrated.
This means there is no output until the sum of the input pulses equals the set time delay
to operate. The output is deactivated when the input signal is FALSE and the time
delay to reset has elapsed.