18.6.6 Function status fault protection for IEC 60870-5-103
I103FLTPROT
18.6.6.1 Functionality
I103FLTPROT is used for fault indications in monitor direction. Each input on the
function block is specific for a certain fault type and therefore must be connected to a
correspondent signal present in the configuration. For example: 68_TRGEN
represents the General Trip of the device, and therefore must be connected to the
general trip signal SMPPTRC_TRIP or equivalent.
The delay observed in the protocol is the time difference in between the signal that is
triggering the Disturbance Recorder and the respective configured signal to the IEC
60870-5-103 I103FLTPROT.
18.6.6.2 Identification
Function description Function block
name
IEC 60617
identification
ANSI/IEEE C37.2
device number
Function status fault protection for IEC
60870-5-103
I103FLTPROT - -
Section 18 1MRK502052-UEN B
Station communication
1036
Technical manual