18.10.3 Function block
IEC10000250-1-en.vsd
GOOSEINTRCV
BLOCK ^INTOUT
DATAVALID
COMMVALID
TEST
IEC10000250 V1 EN
Figure 487: GOOSEINTRCV function block
18.10.4 Signals
Table 797: GOOSEINTRCV Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
Table 798: GOOSEINTRCV Output signals
Name Type Description
INTOUT INTEGER Integer output
DATAVALID BOOLEAN Data valid for integer output
COMMVALID BOOLEAN Communication valid for integer output
TEST BOOLEAN Test output
18.10.5 Settings
Table 799: GOOSEINTRCV Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off/On
18.10.6 Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
The input of this GOOSE block must be linked in SMT by means of
a cross to receive the integer values.