Name Type Description
OUT14 BOOLEAN Output 14
OUT15 BOOLEAN Output 15
OUT16 BOOLEAN Output 16
15.13.5 Settings
This function does not have any setting parameters.
15.13.6 Operation principle
An example is used to explain the principle of operation: With integer 15 sent to and
received by the ITBGAPC function on the IEC 61850 the OUTx changes from 0 to 1
on each of the OUT1; OUT2 OUT3 and OUT4. All other OUTx (5≤x≤16) remains 0.
The boolean interpretation of this is represented by the assigned values of each of the
outputs OUT1 = 1; and OUT2 = 2; and OUT3= 4; and OUT4 = 8. The sum of these
OUTx (1≤x≤4) is equal to the integer 15 received via the IEC 61850 network. The
remaining OUTx = 0 for (5≤x≤16).
OUTx represents a value when activated. The value of each of the OUTx is in
accordance with the Table
601. When not activated the OUTx has the value 0.
The value of each OUTx for 1≤x≤16 (1≤x≤16) follows the general formulae: OUTx
= 2
x-1
The sum of the values of all activated OUTx = 2
x-1
where 1≤x≤16 will be equal
to the integer value received over IEC 61850 to the ITBGAPC_1 function block.
The Integer to Boolean 16 conversion with logic node representation function
(ITBGAPC) will transfer an integer with a value between 0 to 65535 communicated
via IEC 61850 and connected to the ITBGAPC function block to a combination of
activated outputs OUTx where 1≤x≤16. The values represented by the different OUTx
are according to Table
601. When an OUTx is not activated, its value is 0.
The ITBGAPC function is designed for receiving the integer input from a station
computer - for example, over IEC 61850. If the BLOCK input is activated, it will
freeze the logical outputs at the last value.
Table 601: Outputs and their values when activated
Name of OUTx
Type Description Value when
activated
Value when
deactivated
OUT1 BOOLEAN Output 1 1 0
OUT2 BOOLEAN Output 2 2 0
OUT3 BOOLEAN Output 3 4 0
OUT4 BOOLEAN Output 4 8 0
OUT5 BOOLEAN Output 5 16 0
OUT6 BOOLEAN Output 6 32 0
OUT7 BOOLEAN Output 7 64 0
Table continues on next page