INDEXTSPQT can propagate the quality, the value and the time stamps of the signals
via IEC 61850.
15.7.3.1 Function block
INDEXTSPQT
SI_IN* SI_OUT
TIME
BLOCKED
SUBST
INVALID
TEST
IEC14000067-1-en.vsd
IEC14000067 V1 EN
Figure 389: INDEXTSPQT function block
15.7.3.2 Signals
Table 552: INDEXTSPQT Input signals
Name Type Default Description
SI_IN BOOLEAN 0 Single indication
Table 553: INDEXTSPQT Output signals
Name
Type Description
SI_OUT BOOLEAN Single indication
TIME GROUP SIGNAL Timestamp of input
BLOCKED BOOLEAN Blocked for update
SUBST BOOLEAN Substituted
INVALID BOOLEAN Invalid value
TEST BOOLEAN Testmode
15.7.3.3 Technical data
Table 554: Number of INDEXTSPQT instances
Logic block
Quantity with cycle time
3 ms 8 ms 100 ms
INDEXTSPQT - 10 10
15.7.4 Invalid logic function block INVALIDQT
Component which sets quality invalid of outputs according to a "valid" input.
The values of the input signals INPUTx (where 1<x<16) are copied to the outputs
OUTPUTx (where 1<x<16). If the input VALID is 0 or if its quality bit is set invalid,
Section 15 1MRK502052-UEN B
Logic