ABB REG670 - Technical Data

ABB REG670
1298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IEC05000748_2_en.vsd
UN ST1
TR1
ST2
TR2
START
TRIP
Comparator
UN > U1>
Start
t2
tReset2
&
Trip
Output
Logic
Step 2
Phase 1
Phase 1
Time integrator
tIReset2
ResetTypeCrv2
START
Start
t1
tReset1
&
Trip
Output
Logic
Step 1
Time integrator
tIReset1
ResetTypeCrv1
Comparator
UN > U2>
START
TRIP
TRIP
OR
OR
IEC05000748 V2 EN
Figure 248: Schematic design of Two step residual overvoltage protection
ROV2PTOV
9.3.8 Technical data
Table 283: ROV2PTOV technical data
Function
Range or value Accuracy
Operate voltage,
step 1 and step 2
(1.0-200.0)% of
UBase
± 0.5% of U
r
at U ≤ U
r
± 0.5% of U at U > U
r
Absolute
hysteresis
(0.0–50.0)% of
UBase
± 0.5% of U
r
at U ≤ U
r
± 0.5% of U at U > U
r
Inverse time
characteristics for
low and high step,
see table
972
-
See table 972
Definite time delay
low step (step 1) at
0 to 1.2 x U
set
(0.00–6000.00) s ± 0.2% or ± 45 ms whichever is
greater
Definite time delay
high step (step 2)
at 0 to 1.2 x U
set
(0.000–60.000) s ± 0.2% or ± 45 ms whichever is
greater
Table continues on next page
1MRK502052-UEN B Section 9
Voltage protection
515
Technical manual

Table of Contents