15.9.3 Function block
FXDSIGN
OFF
ON
INTZERO
INTONE
INTALONE
REALZERO
STRNULL
ZEROSMPL
GRP_OFF
IEC05000445-3-en.vsd
IEC05000445 V3 EN
Figure 398: FXDSIGN function block
15.9.4 Signals
Table 587: FXDSIGN Output signals
Name Type Description
OFF BOOLEAN Boolean signal fixed off
ON BOOLEAN Boolean signal fixed on
INTZERO INTEGER Integer signal fixed zero
INTONE INTEGER Integer signal fixed one
INTALONE INTEGER Integer signal fixed all ones
REALZERO REAL Real signal fixed zero
STRNULL STRING String signal with no characters
ZEROSMPL GROUP SIGNAL Channel id for zero sample
GRP_OFF GROUP SIGNAL Group signal fixed off
15.9.5 Settings
The function does not have any settings available in Local HMI or Protection and
Control IED Manager (PCM600).
15.9.6 Operation principle
There are nine outputs from FXDSIGN function block:
OFF is a boolean signal, fixed to OFF (boolean 0) value
ON is a boolean signal, fixed to ON (boolean 1) value
INTZERO is an integer number, fixed to integer value 0
INTONE is an integer number, fixed to integer value 1
INTALONE is an integer value FFFF (hex)
REALZERO is a floating point real number, fixed to 0.0 value
Section 15 1MRK502052-UEN B
Logic
836
Technical manual