Loading...
IEC05000521-3.vsd
IEC05000521-WMF V3 EN
Figure 372: Final tripping circuits
15.1.7 Technical data
Table 491: SMPPTRC technical data
Function
Range or value Accuracy
Trip action 3-ph, 1/3-ph, 1/2/3-ph -
Minimum trip pulse length (0.000-60.000) s ± 0.2% or ± 30 ms whichever
is greater
3-pole trip delay (0.020-0.500) s ± 0.2% or ±10 ms whichever is
greater
Single phase delay, two phase
delay and evolving fault delay
(0.000-60.000) s ± 0.2% or ±10 ms whichever is
greater
15.2 Trip matrix logic TMAGAPC
15.2.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Trip matrix logic TMAGAPC - -