Table 836: TIMESYNCHGEN Non group settings (basic)
Name Values (Range) Unit Step Default Description
CoarseSyncSrc Off
SPA
LON
SNTP
DNP
IEC103
-
- Off Coarse time synchronization source
FineSyncSource Off
SPA
LON
BIN
GPS
GPS+SPA
GPS+LON
GPS+BIN
SNTP
GPS+SNTP
IRIG-B
GPS+IRIG-B
PPS
- - Off Fine time synchronization source
SyncMaster Off
SNTP-Server
- - Off Activate IEDas synchronization master
TimeAdjustRate Slow
Fast
- - Fast Adjust rate for time synchronization
HWSyncSrc Off
GPS
IRIG-B
PPS
-
- Off Hardware time synchronization source
AppSynch NoSynch
Synch
- - NoSynch Time synchronization mode for
application
SyncAccLevel Class T5 (1us)
Class T4 (4us)
Unspecified
-
- Unspecified Wanted time synchronization accuracy
Table 837: BININPUT Non group settings (basic)
Name
Values (Range) Unit Step Default Description
ModulePosition 3 - 16 - 1 3 Hardware position of IO module for time
synchronization
BinaryInput 1 - 16 - 1 1 Binary input number for time
synchronization
BinDetection PositiveEdge
NegativeEdge
- - PositiveEdge Positive or negative edge detection
Table 838: SNTP Non group settings (basic)
Name
Values (Range) Unit Step Default Description
ServerIP-Add 0 - 255 IP
Address
1 0.0.0.0 Server IP-address
RedServIP-Add 0 - 255 IP
Address
1 0.0.0.0 Redundant server IP-address
Section 20 1MRK502052-UEN B