Test Type test values Reference standards
Pulse magnetic field
immunity test
1000 A/m IEC 61000–4–9, Class V
Damped oscillatory magnetic
field test
100 A/m IEC 61000-4-10, Class V
Radiated electromagnetic
field disturbance
20 V/m, 80-1000 MHz
1.4-2.7 GHz
IEC 60255-26
Radiated electromagnetic
field disturbance
20 V/m
80-1000 MHz
IEEE/ANSI C37.90.2
Conducted electromagnetic
field disturbance
10 V, 0.15-80 MHz IEC 60255-26
Radiated emission 30-5000 MHz IEC 60255-26
Radiated emission 30-5000 MHz IEEE/ANSI C63.4, FCC
Conducted emission 0.15-30 MHz IEC 60255-26
Table 941: Insulation
Test Type test values Reference standard
Dielectric test 2.0 kV AC, 1 min. IEC 60255-27
ANSI C37.90
Impulse voltage test
5 kV, 1.2/50 ms, 0.5 J
Insulation resistance
>100 MW at 500 VDC
Table 942: Environmental tests
Test
Type test value Reference standard
Cold operation test Test Ad for 16 h at -25°C IEC 60068-2-1
Cold storage test Test Ab for 16 h at -40°C IEC 60068-2-1
Dry heat operation test Test Bd for 16 h at +70°C IEC 60068-2-2
Dry heat storage test Test Bb for 16 h at +85°C IEC 60068-2-2
Change of temperature test Test Nb for 5 cycles at -25°C
to +70°C
IEC 60068-2-14
Damp heat test, steady state Test Ca for 10 days at +40°C
and humidity 93%
IEC 60068-2-78
Damp heat test, cyclic Test Db for 6 cycles at +25 to
+55°C and humidity 93 to
95% (1 cycle = 24 hours)
IEC 60068-2-30
Table 943: CE compliance
Test
According to
Immunity EN 60255–26
Emissivity EN 60255–26
Low voltage directive EN 60255–27
Section 21 1MRK502052-UEN B
IED hardware
1218
Technical manual