Name Values (Range) Unit Step Default Description
TimerLinksZ1 LoopLink (tPP-tPE)
LoopLink &
ZoneLink
No Links
-
- LoopLink (tPP-
tPE)
How start of trip delay timers should be
linked for zone 1
TimerModeZ2 Disable all
Enable Ph-E
Enable PhPh
Enable Ph-E PhPh
-
- Enable Ph-E PhPh On/Off setting for Ph-Ph and Ph-E trip
output, zone 2
TimerLinksZ2 LoopLink (tPP-tPE)
LoopLink &
ZoneLink
No Links
-
- LoopLink (tPP-
tPE)
How start of trip delay timers should be
linked for zone 2
TimerModeZ3 Disable all
Enable Ph-E
Enable PhPh
Enable Ph-E PhPh
-
- Enable Ph-E PhPh On/Off setting for Ph-Ph and Ph-E trip
output, zone 3
TimerLinksZ3 LoopLink (tPP-tPE)
LoopLink &
ZoneLink
No Links
-
- LoopLink (tPP-
tPE)
How start of trip delay timers should be
linked for zone 3
TimerModeZ4 Disable all
Enable Ph-E
Enable PhPh
Enable Ph-E PhPh
-
- Enable Ph-E PhPh On/Off setting for Ph-Ph and Ph-E trip
output, zone 4
TimerLinksZ4 LoopLink (tPP-tPE)
LoopLink &
ZoneLink
No Links
-
- LoopLink (tPP-
tPE)
How start of trip delay timers should be
linked for zone 4
TimerModeZ5 Disable all
Enable Ph-E
Enable PhPh
Enable Ph-E PhPh
-
- Enable Ph-E PhPh On/Off setting for Ph-Ph and Ph-E trip
output, zone 5
TimerLinksZ5 LoopLink (tPP-tPE)
LoopLink &
ZoneLink
No Links
-
- LoopLink (tPP-
tPE)
How start of trip delay timers should be
linked for zone 5
TimerModeZRV Disable all
Enable Ph-E
Enable PhPh
Enable Ph-E PhPh
-
- Enable Ph-E PhPh On/Off setting for Ph-Ph and Ph-E trip
output, zone RV
TimerLinksZRV LoopLink (tPP-tPE)
LoopLink &
ZoneLink
No Links
-
- LoopLink (tPP-
tPE)
How start of trip delay timers should be
linked for zone RV
Table 96: ZMFCPDIS Non group settings (basic)
Name
Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
Section 7 1MRK502052-UEN B
Impedance protection
236
Technical manual