Apparent generator
impedance
Pole slip
impedance
movement
IEC06000437 V2 EN
Figure 107: Movements in the impedance plain
where:
X'
d
= transient reactance of the generator
X
T
= short-circuit reactance of the step-up transformer
Z
S
= impedance of the power system A
The detection of rotor angle is enabled when:
the minimum current exceeds 0.10 I
N
(I
N
is IBase parameter set under general
setting).
the maximum voltage falls below 0.92 UBase
the voltage Ucosφ (the voltage in phase with the generator current) has an angular
velocity of 0.2...8 Hz and
the corresponding direction is not blocked.
Section 7 1MRK502052-UEN B
Impedance protection
256