IEC11000011 V1 EN
Figure 139: Injection via open delta VT connection
It must be observed that the resistor R
d
is normally applied for ferro-resonance
damping. The resistance R
d
is will have very little contribution to the earth fault
current as it has high resistance. This injection principle can be used for applications
1MRK502052-UEN B Section 7
Impedance protection
309
Technical manual