Name Values (Range) Unit Step Default Description
OpModeZ2 Off
PP Loops
EnhancedReach
-
- EnhancedReach Operation mode of Zone 2: Off/Ph-Ph/
EnhancedReach
Z2Fwd 3.0 - 200.0 % Zb 0.1 15.0 Zone 2 forward reach in % of rated
impedance, 100%=full load
Z2Rev 3.0 - 200.0 % Zb 0.1 8.0 Zone 2 reverse reach in % of rated
impedance, 100%=full load
tZ2 0.000 - 60.000 s 0.001 0.500 Time delay to operate for Zone 2
OpModeZ3 Off
PP Loops
EnhancedReach
-
- EnhancedReach Operation mode of Zone 3: Off/Ph-Ph/
EnhancedReach
Z3Fwd 3.0 - 200.0 % Zb 0.1 75.0 Zone 3 forward reach in % of rated
impedance, 100%=full load
Z3Rev 3.0 - 200.0 % Zb 0.1 8.0 Zone 3 reverse reach in % of rated
impedance, 100%=full load
tZ3 0.000 - 60.000 s 0.001 1.500 Time delay to operate for Zone 3
OpModeU< Off
Z2Start
Z3Start
-
- Off Enable under voltage seal in (Off/Z2Start/
Z3Start)
U< 5 - 90 %UB 1 70 Start value of under voltage seal in
tU< 0.000 - 60.000 s 0.001 5.000 Time delay to operate for under voltage
seal in
Table 147: ZGVPDIS Group settings (advanced)
Name
Values (Range) Unit Step Default Description
RLd 5 - 120 % Zb 1 50 Resistive reach in % for load
encroachment charateristics
ArgLd 5 - 85 Deg 1 38 Load encroachment inclination of load
angular sector
LoadEnchModZ2 Off
On
- - Off Enable load encroachement for Zone 2
Off/On
LoadEnchModZ3 Off
On
- - On Enable load encroachement for Zone 3
Off/On
Table 148: ZGVPDIS Non group settings (basic)
Name
Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups