Name Values (Range) Unit Step Default Description
Characterist2 ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
- - ANSI Def. Time Time delay characteristic for step 2
IN2> 1 - 2500 %IB 1 50 Residual current operate level for step 2 in
% of IBase
t2 0.000 - 60.000 s 0.001 0.400 Time delay of step 2 when definite time
char. is selected
k2 0.05 - 999.00 - 0.01 0.05 Time multiplier for the step 2 selected time
characteristic
IMin2 1.00 - 10000.00 %IB 1.00 50 Minimum operate residual current for step
2 in % of IBase
t2Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse time
characteristic step 2
IN2Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for the residual current setting
value for step 2
HarmBlock2 Off
On
- - On Enable block of step 2 from harmonic
restrain
DirMode3 Off
Non-directional
Forward
Reverse
-
- Non-directional Directional mode of step 3 (Off, Non-dir,
Forward, Reverse)
Characterist3 ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
- - ANSI Def. Time Time delay characteristic for step 3
IN3> 1 - 2500 %IB 1 33 Residual current operate level for step 3 in
% of IBase