where it is sufficient to detect failure to open (high current) in one pole or high
residual current and 2 out of 4 where at least two current (phase current and/or
residual current) shall be high for breaker failure detection.
The current detection level for the residual current can be set different from the
setting of phase current detection.
It is possible to have different back-up time delays for single-phase faults and for
multi-phase faults.
The back-up trip can be made without current check. It is possible to have this
option activated for small load currents only.
It is possible to have instantaneous back-up trip function if a signal is high if the
circuit breaker is insufficient to clear faults, for example at low gas pressure.
S
R
SR
Q
OR
AND
AND
30 ms
t
150 ms
START
STL1
OR
OR
BackupTrip L1
BFP Started L1
Time out L1
Reset L1
BLOCK
Retrip Time Out L1
IEC09000976-1-en.vsd
IEC09000976 V1 EN
Figure 185: Simplified logic scheme of the CCRBRF starting logic
AND
AND
AND
AND
AND
OR
OR
OR
a
b
a>b
AND
a
b
a>b
I>BlkCont
AND
Time out L1
BFP Started L1
Reset L1
CBCLDL1
IL1
Current High L1
Contact Closed L1
IEC09000977-1-en.vsd
FunctionMode
OR
OR
Current
Contact
Current and Contact
1
IP>
CB Closed L1
IEC09000977 V1 EN
Figure 186: Simplified logic scheme of the CCRBRF, CB position evaluation
1MRK502052-UEN B Section 8
Current protection
411
Technical manual