Name Values (Range) Unit Step Default Description
CTStarPoint4 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec4 1 - 10 A 1 1 Rated CT secondary current
CTprim4 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint5 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec5 1 - 10 A 1 1 Rated CT secondary current
CTprim5 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint6 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec6 1 - 10 A 1 1 Rated CT secondary current
CTprim6 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint7 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec7 1 - 10 A 1 1 Rated CT secondary current
CTprim7 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint8 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec8 1 - 10 A 1 1 Rated CT secondary current
CTprim8 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint9 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec9 1 - 10 A 1 1 Rated CT secondary current
CTprim9 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint10 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec10 1 - 10 A 1 1 Rated CT secondary current
CTprim10 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint11 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec11 1 - 10 A 1 1 Rated CT secondary current
CTprim11 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint12 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec12 1 - 10 A 1 1 Rated CT secondary current
CTprim12 1 - 99999 A 1 3000 Rated CT primary current
Table 10: TRM_6I_6U Non group settings (basic)
Name
Values (Range) Unit Step Default Description
CTStarPoint1 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec1 1 - 10 A 1 1 Rated CT secondary current
CTprim1 1 - 99999 A 1 3000 Rated CT primary current
Table continues on next page
1MRK502052-UEN B Section 3
Analog inputs
67
Technical manual