14.4 Voltage control
14.4.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Tap changer control and supervision, 6
binary inputs
TCMYLTC - 84
Tap changer control and supervision, 32
binary inputs
TCLYLTC - 84
14.4.2 Functionality
Tap changer control and supervision, 6 binary inputs TCMYLTC as well as Tap
changer control and supervision, 32 binary inputs TCLYLTC are is used for control
of power transformers with a on-load tap changer. The functions provide automatic
regulation of the voltage on the secondary side of transformers or alternatively on a
load point further out in the network.
Control of a single transformer, as well as control of up to eight transformers in
parallel is possible. For parallel control of power transformers, three alternative
1MRK502052-UEN B Section 14
Control
743
Technical manual

Table of Contents