Name Values (Range) Unit Step Default Description
Operation37 Off
On
- - Off Operation On/off
Operation38 Off
On
- - Off Operation On/off
Operation39 Off
On
- - Off Operation On/off
Operation40 Off
On
- - Off Operation On/off
Table 684: A4RADR Non group settings (advanced)
Name Values (Range) Unit Step Default Description
NomValue31 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 31
UnderTrigOp31 Off
On
- - Off Use under level trigger for analog channel
31 (on) or not (off)
UnderTrigLe31 0 - 200 % 1 50 Under trigger level for analog channel 31
in % of signal
OverTrigOp31 Off
On
- - Off Use over level trigger for analog channel
31 (on) or not (off)
OverTrigLe31 0 - 5000 % 1 200 Over trigger level for analog channel 31 in
% of signal
NomValue32 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 32
UnderTrigOp32 Off
On
- - Off Use under level trigger for analog channel
32 (on) or not (off)
UnderTrigLe32 0 - 200 % 1 50 Under trigger level for analog channel 32
in % of signal
OverTrigOp32 Off
On
- - Off Use over level trigger for analog channel
32 (on) or not (off)
OverTrigLe32 0 - 5000 % 1 200 Over trigger level for analog channel 32 in
% of signal
NomValue33 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 33
UnderTrigOp33 Off
On
- - Off Use under level trigger for analog channel
33 (on) or not (off)
UnderTrigLe33 0 - 200 % 1 50 Under trigger level for analog channel 33
in % of signal
OverTrigOp33 Off
On
- - Off Use over level trigger for analog channel
33 (on) or not (off)
OverTrigLe33 0 - 5000 % 1 200 Overtrigger level for analog channel 33 in
% of signal
NomValue34 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 34
UnderTrigOp34 Off
On
- - Off Use under level trigger for analog channel
34 (on) or not (off)
UnderTrigLe34 0 - 200 % 1 50 Under trigger level for analog channel 34
in % of signal
OverTrigOp34 Off
On
- - Off Use over level trigger for analog channel
34 (on) or not (off)
OverTrigLe34 0 - 5000 % 1 200 Over trigger level for analog channel 34 in
% of signal