EasyManua.ls Logo

GE Multilin F650

GE Multilin F650
533 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GE Multilin F650 Digital Bay Controller 5-41
5 SETPOINTS 5.4 PROTECTION ELEMENTS
5
5.4.3.2 PHASE INSTANTANEOUS OVERCURRENT UNIT- PHASE IOC (50PH/ 50PL)
The 50P phase instantaneous overcurrent unit has a setpoint range from 0.05 A to 160 A, which can be set as
instantaneous or timed, with a timer selectable between 0.00 and 900 seconds. The phase current input quantities may be
programmed as Fundamental phasor magnitude or total waveform RMS magnitude as required by the application. The unit
incorporates a reset time selectable between 0 and 900 seconds.
This unit incorporates a block input for disabling the pickup and trip signals. The logic outputs are the pickup and trip flags
independent for each phase, and general pickup and trip flags for the unit.
Table 5–39: 50PH/50PL UNIT SETPOINTS
The snapshot event setpoint enables or disables the snapshot event generation for the phase instantaneous overcurrent
units.
SETPOINT > PROTECTION ELEMENTS > PHASE CURRENT >
> PHASE IOC HIGH > PHASE IOC HIGH 1> PHASE IOC HIGH 2 > PHASE IOC HIGH 3
> PHASE IOC LOW > PHASE IOC LOW 1 > PHASE IOC LOW 2 > PHASE IOC LOW 3
SETPOINT DESCRIPTION NAME DEFAULT VALUE STEP RANGE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Input type Input PHASOR(DFT) N/A [PHASOR – RMS]
Pickup level Pickup Level 30.00 0.01 A [0.05 : 160.00]
Trip time Trip Delay 0.00 0.01 s [0.00 : 900.00]
Reset time Reset Delay 0.00 0.01 s [0.00 : 900.00]
Snapshot event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]

Table of Contents

Other manuals for GE Multilin F650

Related product manuals