GE Multilin F650 Digital Bay Controller 5-95
5 SETPOINTS 5.5 CONTROL ELEMENTS
5
Signals relative to breaker failure provided by the relay can be viewed at Actual> Status > Control Elements > Breaker
Failure, and they are as follows:
Table 5â79: BREAKER FAILURE STATUS
BKR FAIL INITIATE External signal for breaker failure initiation. (Configurable at setpoints> Relay
Configuration > Protection Elements).
BKR FAIL NO CURRENT Signal for breaker failure without current
BKR FAIL SUPERVISION Signal for supervision level breaker failure (retrip)
BKR FAIL HISET Signal for high-level breaker failure
BKR FAIL LOWSET Signal for low-level breaker failure
INTERNAL ARC Signal for internal arc
BKR FAIL 2nd STEP Signal for Second level breaker failure (high and low)