10-4 F650 Digital Bay Controller GE Multilin
10.1 EXAMPLE1: COMMUNICATION & PROTECTION SETTINGS PROCEDURE 10 APPLICATION EXAMPLES
10
Under
SETPOINT  RELAY CONFIGURATION  OPERATIONS
SelectÂŁ Operation 0
Command TextReset C Output 00
Interlock Type None
Interlocks---
Final State TypeNone
Final States---
Frontal KeyF1
Contact InputNone
Virtual OutputNone
Time Out500 (default)
MMI---
Com1---
Com 2---
ETH-Master 1---
ETH Master 2---
ETH Master 3---
ETH Mastef 4---
Under
SETPOINT  RELAY CONFIGURATION  OSCILLOGRAPHY
10.1.4 TEST
Apply 7.5 A in phase A (terminals B1-B2) until contact 00 on Board F operates (terminals F19-F21 should be and remain
closed), and LED 5 should be lit. Check that operating time is in the order of 1.7 seconds.
Remove current from terminals B1-B2
Press pushbutton F1 and check that contact 00 on Board F has been open.
Check that LED 5 in the front of the relay has been turned off.
Repeat the process for phase B (terminals B3-B4) and for phase C (terminals B5-B6)
Under Actual  Waveform Capture menu retrieve the last oscillography recording stored, open it using GE_OSC program
and check that the two digital signals as well as the current signal were kept.
ÂŁ Led 5 C Output Op 00 C Output_00_00
SELECT NAME SOURCE
ÂŁ Digital Channel 1 C Output Op_00_00 C Output Oper_00_00
ÂŁ Digital Channel 2 C Output_00_00 C Output_00_00

Table of Contents

Other manuals for GE Multilin F650

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Multilin F650 and is the answer not in the manual?

GE Multilin F650 Specifications

General IconGeneral
BrandGE
ModelMultilin F650
CategoryController
LanguageEnglish

Related product manuals