2-10 F650 Digital Bay Controller GE Multilin
2.4 TECHNICAL SPECIFICATIONS 2 PRODUCT DESCRIPTION
2
j) PHASE DIRECTIONAL (67P)
k) GROUND DIRECTIONAL (67G)
l) NEUTRAL DIRECTIONAL (67N)
Saturation Level 48 times the pickup level
Snapshot Events Selectable by setting
Directionality Forward and reverse selectable by setting
Polarizing Quadrature Voltage:
ABC seq: Phase A (VBC), Phase B (VCA), Phase C
(VAB)
ACB seq: Phase A (VCB), Phase B (VAC), Phase C
(VBA)
Polarizing voltage threshold 0 to 300 Vac in steps of 1 V
Characteristic angle -90º to +90º in steps of 1º
Block Logic Permission or Block selectable by setting
Angle accuracy
2º for I>0.1 A and V>5 Vac
Operate time <30ms, typically
Directionality Forward and reverse selectable by setting
Polarizing Voltage, current, dual
Polarizing Voltage V
N
(measured or calculated, selected by setting)
Polarizing Current
Isg (measured from 5
th
current transformer)
Operating Current
Ig (measured from 4
th
current transformer)
Polarizing Voltage threshold 0 to 300 Vac in steps of 1 V
Polarizing Current threshold 0.005 A
Characteristic angle -90º to +90º in steps of 1º
Block Logic Permission or Block selectable by setting
Angle accuracy
2º for I>0.1 A and V>5 Vac
Operate time <30ms, typically
Directionality Forward and reverse selectable by setting
Polarizing Voltage, current, dual
Polarizing Voltage V
N
(measured or calculated, selected by setting)
Polarizing Current
Isg (measured from 5
th
current transformer)
Operating Current I
N
Polarizing Voltage threshold 0 to 300 Vac in steps of 1 V
Polarizing Current threshold 0.005 A
Characteristic angle -90º to +90º in steps of 1º
Block Logic Permission or Block selectable by setting