GE Multilin F650 Digital Bay Controller 5-105
5 SETPOINTS 5.6 INPUTS/OUTPUTS
5
5.6.3.2 INPUT STATUS SIGNALS
Actual > Inputs/Outputs > Contact inputs > Board X (being X the corresponding board in each case). Depending on the
I/O board, inputs are represented as follows:
Table 5–87: CONTACT INPUTS STATUS
The operation logic for supervision signals (board type 2) is detailed in section . in this manual.
INPUT STATUS
(X: BOARD F, G, H, J)
MIXED BOARD
(TYPE 1)
SUPERVISION BOARD
(TYPE 2)
CONT IP_X_CC1 CC1 CC1
CONT IP_X_CC2 CC2 CC2
CONT IP_X_CC3 CC3 CC3
CONT IP_X_CC4 CC4 CC4
CONT IP_X_CC5 CC5 CC5
CONT IP_X_CC6 CC6 CC6
CONT IP_X_CC7 CC7 CC7
CONT IP_X_CC8 CC8 CC8
CONT IP_X_CC9 CC9 Va_COIL1
CONT IP_X_CC10 CC10 Vb_COIL1
CONT IP_X_CC11 CC11 Va_COIL2
CONT IP_X_CC12 CC12 Vb_COIL2
CONT IP_X_CC13 CC13 O7_SEAL
CONT IP_X_CC14 CC14 O8_SEAL
CONT IP_X_CC15 CC15 SUP_COIL1
CONT IP_X_CC16 CC16 SUP_COIL2