2-12 F650 Digital Bay Controller GE Multilin
2.4 TECHNICAL SPECIFICATIONS 2 PRODUCT DESCRIPTION
2
p) PHASE UNDERVOLTAGE (27P)
q) NEUTRAL OVERVOLTAGE (59NH/59NL)
r) NEGATIVE SEQUENCE OVERVOLTAGE (47)
s) AUXILIARY OVERVOLTAGE (59X)
Voltage Input Fundamental Phasor of phase-to-ground or phase-to-
phase voltages (selectable by setting)
Pickup level 3 to 300 in steps of 1 V
Reset level 103% of the pickup level
Level accuracy
1% reading 0.1% Full Scale from 10 to 275 V
Curve Shapes Fixed time or inverse curve
Reset type Instantaneous
Curve Multiplier (Time Dial) 0.00 to 900.00 s. in steps of 0.01 s.
Timing accuracy ±3.5% of operate time or 30 ms. (whichever is greater)
Minimum Voltage Threshold 0 to 300 in steps of 1 V
Logic Any/Two/All phases logic selectable by setting
Supervised by Breaker Selectable by setting
Snapshot Events Selectable by setting
Voltage Input Fundamental Phasor of the neutral voltage
Pickup level 3 to 300 in steps of 1 V
Reset level 97% of the pickup level
Level accuracy
1% reading 0.1% Full Scale from 10 to 275 V
Trip delay 0.00 to 900.00 s. in steps of 0.01 s
Reset delay 0.00 to 900.00 s. in steps of 0.01 s
Timing accuracy ±3.5% of operate time or 30 ms. (whichever is greater)
Snapshot Events Selectable by setting
Voltage Input Fundamental Phasor
Pickup level 3 to 300 in steps of 1 V
Reset level 97% of the pickup level
Level accuracy
1% reading 0.1% Full Scale from 10 to 275 V
Trip delay 0.00 to 900.00 s. in steps of 0.01 s
Reset delay 0.00 to 900.00 s. in steps of 0.01 s
Timing accuracy ±3.5% of operate time or 30 ms. (whichever is greater)
Snapshot Events Selectable by setting
Voltage Input Fundamental Phasor
Pickup level 3 to 300 in steps of 1 V
Reset level 97% of the pickup level