2-20 F650 Digital Bay Controller GE Multilin
2.4 TECHNICAL SPECIFICATIONS 2 PRODUCT DESCRIPTION
2
e) USER-PROGRAMMABLE FRONT KEYS
2.4.5 METERING
a) CURRENT
b) VOLTAGE
c) REAL POWER (WATTS)
d) REACTIVE POWER (VARS)
e) APPARENT POWER (VA)
f) WATT-HOURS (POSITIVE AND NEGATIVE)
g) WAR-HOURS (POSITIVE AND NEGATIVE)
h) POWER FACTOR
Number of configurable Keys: 5
Operation: drive PLC operands
Accuracy:
î™Č0.5% of the reading î™Č 10 mA from 0.05 to 10 A (for phases and ground)
î™Č1.5% of the reading î™Č 1 mA from 0.005 to 5 A (for sensitive ground)
î™Č1.5% of the reading for higher values
Accuracy:
î™Č1% reading î™Č0.1% Full Scale from 10 to 275 V
Accuracy:
î™Č1% of the reading at-0.8 < PF = -1 and 0.8 <PF=1
Accuracy:
î™Č1% of the reading at-0.2 = PF = 0.2
Accuracy:
î™Č1% of the reading
Accuracy:
î™Č1% of the reading
Range:
î™Č0 to 2147 MWh
Parameters: 3-phase only
Update rate: 100 ms
Accuracy:
î™Č1% of the reading
Range:
î™Č0 to 2147 MVArh
Parameters: 3-phase only
Update rate: 100 ms
Accuracy: 0.02
Parameters: 3-Phase and single phase

Table of Contents

Other manuals for GE Multilin F650

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Multilin F650 and is the answer not in the manual?

GE Multilin F650 Specifications

General IconGeneral
BrandGE
ModelMultilin F650
CategoryController
LanguageEnglish

Related product manuals