2-14 F650 Digital Bay Controller GE Multilin
2.4 TECHNICAL SPECIFICATIONS 2 PRODUCT DESCRIPTION
2
w) FORWARD POWER (32FP)
x) SENSITIVE DIRECTIONAL POWER (32)
y) BROKEN CONDUCTOR (I2/I1)
Note: The I2/I1 current inhibition level for the different
firmware versions is as follows
Current, Voltage Fundamental Phasor (primary values)
Number of stages 2
Pickup level (two stages) 0.00-10000.00 MW in steps of 0.01 MW
Reset level 97% of the pickup level
Level accuracy for primary magnitudes ±3% complete range.
Trip delay (two stages) 0.00 to 900.00 s in steps of 0.01 s
Timing accuracy ±3.5% of operate time or 30 ms. (whichever is greater)
Block Time after close 0.00 to 900.00 s in steps of 0.01 s
Snapshot Events Selectable by setting
Current, Voltage Fundamental Phasor (primary values)
Number of stages 2
Pickup level (two stages) -10000.00 to 10000.00 MW (primary values) in steps of
0.01 MW
Characteristic Angle (two stages) 0.00 to 359.99 in steps of 0.01
Reset level 97% of the pickup level
Accuracy for primary magnitudes ±3% complete range
Trip delay (two stages) 0.00 to 900.00 s in steps of 0.01 s
Timing accuracy ±3.5% of operate time or 30 ms. (whichever is greater)
Block Time after close 0.00 to 900.00 s in steps of 0.01 s
Snapshot Events Selectable by setting
Pickup level 20.0-100.0% (I2/I1 ratio) in steps of 0.1%
Reset level 97% of the pickup level
Trip delay 0.00 to 900.00 s in steps of 0.01 s
Timing accuracy ±3.5% of operate time or 30 ms. (whichever is greater)
Minimum Phase Current Threshold 0.05 A
Snapshot Events Selectable by setting
Operation Threshold
0.000 to 1.000 A in steps of 0.001 A
Firmware Version Current Inhibition Level
1.50 or Lower 10 mA
1.60 or Higher 50 mA
1.80 or Higher Selectable by setting from 0.000 to 1.000 in steps of 0.001 A