EasyManuals Logo

GE Multilin F650 User Manual

GE Multilin F650
533 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #46 background imageLoading...
Page #46 background image
GE Multilin F650 Digital Bay Controller 2-19
2 PRODUCT DESCRIPTION 2.4 TECHNICAL SPECIFICATIONS
2
2.4.4 USER –PROGRAMABLE ELEMENTS
a) PLC LOGIC
b) FLEXCURVES
c) USER-PROGRAMMABLE LEDS
d) USER-DEFINABLE DISPLAYS
Programming language: The logical configuration is performed using graphical functions based on the
IEC 61131-3 standard.
Lines of code: 512
Supported operations: NOT, XOR, OR (2 to 8 inputs), AND (2 to 8 inputs), NOR (2 to 8 inputs),
NAND (2 to 8 inputs), Latch (Reset Dominant), Edge Detectors, Timers.
2 inputs default gates, from 3 to 8 inputs provided in library format.
Libraries: Logical gates fully programmable by user. To create user-programmable logic to
be distributed as a single object.
Inputs: Any logical variable, contact or virtual input
Number of timers: 8 maximum in each logic scheme (provided in library format)
Number: 4 (A through D)
Reset points: 40 (0 through 1 of pickup)
Operate points: 80 (1 through 20 of pickup)
Time delay: 0 to 65535 ms in steps of 1
Saturation Level 20 times the pickup level
Number: 15 configurable LEDs plus a ready non configurable LED
Programmability: from any logical variable, contact, or virtual input
Reset mode: Self-reset or Latched.
The first 5 LED’s are latched by hardware (red color ones), usually configured for
trip signals.
The following 10 ones (yellow and green) are self-reset but can be latched
through PLC configuration.
Reset Signal: The LED’s can be reset by hardware, pressing the front “esc” key during more
than 3 seconds or using the LED reset signal through PLC configuration.
Number of configurable displays: 1 (one line diagram fully configurable). In graphical displays only
Number of fixed displays: 6, Metering (in primary values), Snapshot events (all and new), Alarms, Inputs
and outputs screen with test functionality for inputs and outputs. In graphical dis-
plays only
Number of selectable displays: Logotype, metering or both in scrolling mode, can be selectable as default
screen in text display for all models (basic and mimic). The metering screen con-
tains current and voltages for phases and ground in primary values.

Table of Contents

Other manuals for GE Multilin F650

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Multilin F650 and is the answer not in the manual?

GE Multilin F650 Specifications

General IconGeneral
BrandGE
ModelMultilin F650
CategoryController
LanguageEnglish

Related product manuals