5-88 F650 Digital Bay Controller GE Multilin
5.5 CONTROL ELEMENTS 5 SETPOINTS
5
5.5.5.3 AUTORECLOSE INPUTS
For the correct operation of the autoreclose element, it is required to configure several input signals in the Relay. These
signals can be configured using EnerVista 650 Setup software, at Setpoint > Relay Configuration > Protection
Elements. The Protection Elements screen allows to select simple signals provided directly by the relay (states), or to
use more complex logics using virtual outputs, configured at setpoint > Logic Configuration using the PLC Editor tool
inside EnerVista 650 Setup.
Actual> Status > Control Elements > Autoreclose
Table 5–76: 79 CONFIGURABLE INPUTS
AR LEVEL BLOCK: This signal is configured to block the autoreclose by level; when the block signal disappears, the
recloser goes to Lockout status before returning to either the READY status, or the
corresponding status in the reclosing cycle.
AR PULSE BLOCK: This signal is configured to block the autoreclose by pulse; a pulse moves the autoreclose to
BLOCK status. The autoreclose block is active until an unblock signal is received.
AR PULSE UNBLOCK: This signal is configured as autoreclose unblock by pulse; this pulse is required to bring the
recloser out of the block status. The autoreclose goes to Lockout after a block situation.
AR INITIATE: This signal indicates the autoreclose initiation. Usually, the factory default configuration sets this
signal as a combination of the general trip signal (Virtual Output 83), and an external input
configured as AR Initiate.
AR CONDS INPUT: This signal configures the conditions that are to be met before executing a breaker close
command. These conditions are verified once the configured Dead Time has expired, and they
are only considered if the Cond. Permission setpoint is enabled. Otherwise, these conditions
wouldn’t have any effect. In the default factory configuration, the conditions input is associated to
the synchronism check element close permission.
AUTORECLOSE INPUTS
AR LEVEL BLOCK
AR PULSE BLOCK
AR PULSE UNBLOCK
AR INITIATE
AR CONDS INPUT

Table of Contents

Other manuals for GE Multilin F650

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Multilin F650 and is the answer not in the manual?

GE Multilin F650 Specifications

General IconGeneral
BrandGE
ModelMultilin F650
CategoryController
LanguageEnglish

Related product manuals