GE Multilin F650 Digital Bay Controller 11-5
11 FREQUENTLY ASKED QUESTIONS 11.4 RELAY CONFIGURATION
11
11.4RELAY CONFIGURATION
Q1 Does the "Service" contact on the Power Supply board cover all possible failures or do I have to create an
output on the I/O board that includes all the internal errors I can access in the logic?
A1 The power supply ready contact only monitor hardware failures in the power supply, to monitor the internal error of
the unit it is necessary to configure a virtual output to and the assign it to the device desired (contact output, LED,
etc.).
Q2 I set an output contact as "Latched". If I do not set a "reset" condition, will it reset from the "ESC" key?
A2 No, you have to configure the contact output reset signal (in Settings>Relay Configuration>Outputs). The ESC
key only reset the LED indicators.