C-14 F650 Digital Bay Controller GE Multilin
C.1 DNP 3.0 PROTOCOL FOR F650 APPENDIX C
C
Figure C–5: SETTINGS FOR DNP3.0 MULTI-MASTER COMMUNICATIONS WITH F650
DNP 3.0 Slave – F650
Ethernet Config
IP Addr: 192.168.37.20
Netmask: 255.255.255.0
DNP 3.0 slave 1
Physical Port: Network
A
ddress: 255
IP Addr Cli1: 192.168.37.1
TCP/UDP Port : 20000
Unsol Dest Addr: 200
DNP 3.0 Master 1
Ethernet Config
IP Addr: 192.168.37.1
Netmask: 255.255.255.0
DNP3 over TCP/IP
DNP Addr: 200
DNP Dest Addr: 255
IP Dest: 192.168.37.20
TCP Dest Port: 20000
DNP 3.0 Master 2
Ethernet Config
IP Addr: 192.168.37.2
Netmask: 255.255.255.0
DNP3 over TCP/IP
DNP Addr: 201
DNP Dest Addr: 256
IP Dest : 192.168.37.20
TCP Dest Port: 20001
DNP 3.0 Master 3
Ethernet Config
IP Addr: 192.168.37.3
Netmask: 255.255.255.0
DNP3 over TCP/IP
DNP Addr: 202
DNP Dest Addr: 257
IP Dest: 192.168.37.20
TCP Dest Port: 20002
DNP 3.0 slave 2
Physical Port: Network
A
ddress: 256
IP Addr Cli1: 192.168.37.2
TCP/UDP Port : 20001
Unsol Dest Addr: 201
DNP 3.0 slave 3
Physical Port: Network
A
ddress: 257
IP Addr Cli1: 192.168.37.3
TCP/UDP Port : 20002
Unsol Dest Addr: 202