F-14 F650 Digital Bay Controller GE Multilin
F.1 FACTORY DEFAULT CONFIGURATION APPENDIX F
F
SETPOINT > CONTROL ELEMENTS > SETTING GROUP
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Setting Grouping Permission Function DISABLED N/A [DISABLED – ENABLED]
Active Group Active Group GROUP 1 N/A
[GROUP 1 – GROUP 2 –
GROUP 3]
Snapshot Event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > UNDERFREQUENCY
UNDERFREQUENCY 1 > UNDERFREQUENCY 2 > UNDERFREQUENCY 3
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Pickup level Pickup Level 49.50 0.01 Hz [20.00 : 65.00]
Trip time Trip Delay 0.00 0.01 s [0.00 : 900.00]
Reset time Reset Delay 0.00 0.01 s [0.00 : 900.00]
Minimum voltage threshold Minimum Voltage 30 1 V [30 : 300]
Snapshot event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > OVERFREQUENCY
OVERFREQUENCY 1 > OVERFREQUENCY 2 > OVERFREQUENCY 3
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Pickup level Pickup Level 50.50 0.01 Hz [20.00 : 65.00]
Trip time Trip Delay 0.00 0.01 s [0.00 : 900.00]
Reset time Reset Delay 0.00 0.01 s [0.00 : 900.00]
Minimum voltage threshold Minimum Voltage 30 1 V [30 : 300]
Snapshot event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]