Page #532 background image
GE Multilin F650 Digital Bay Controller G-3
APPENDIX G G.1 MISCELLANEOUS
G
FIRMWARE
VERSION
BOOT
PROGRAM
VERSION
CHANGES DESCRIPTION MODELS DATE
1.80 2.35 USER INTERFACE
HMI:
New languages available: Russian and Spanish.
Russian/English (P in ordering code, basic display only)
Spanish/English (S in ordering code)
ENERVISTA F650 SETUP
New languages available: Russian and Spanish.
Passwords included in EnerVista F650 Setup (different from the
HMI ones).
WEB SERVER
Multilingual visualization of snapshot events, control events,
oscillography, fault recorder, data logger, metering. New
languages available: Russian and Spanish.
Visualization Enhancement.
COMMUNICATIONS
Modbus TCP communications enhacement.
External CAN interruptions management enhancement.
METERING
Decimal point included in PT and CT ratios.
Power Factor measurement enhancement.
PROTECTION
Function 48 included.
I2/I1 setting to select the minimum inhibition current level of the
unit .
TOC operation level at 1.03 times the pickup (1.05 in previous
releases).
Neutral units measures management enhancement.
Startup Enhancement.
REGISTER
Time Stamp for switchgear control events enhancement.
ALL
March 1
st
2005
1.82 4.00 File system management enhancement in boot code 4.00
Measurements enhancement in 1.82 firmware version
Versions 1.8X can not be upgraded to 2.XX firmware version
without hardware change.
ALL October 17th
2005
2.20 4.00 USER INTERFACE
ENERVISTA F650 SETUP·
- Data Logger visualization changes.·
- File name available in "Config file converter" tool.
COMMUNICATIONS·
- DNP Scale factor correction.·
- IRIGB synchronization:
- Date and time synchronization available.
- 980 ms delay correction.
INPUTS/OUTPUTS·
- Inputs Activation/Deactivation correction.·
- Voltage threshold setting range from 20 to 230 Vdc.·
- Debounce time settings:
- Timestamp before debounce time
- Setting range from 1 to 50 ms.
METERING·
- Power calculations using ARON method.·
- New measurements provided when using Delta connection
and VN as auxiliary voltage input:
- Neutral voltage available.
- Phase to ground voltages available.
- Single phase power measurements available.
PROTECTION·
- Neutral, ground and sensitive ground directional units
available with delta connection and VN as auxiliary voltage
input.·
- Minor changes in Forward Power elements.
REGISTER·
- Ground current available in Fault report.·
- Corrected 150 ms delay in Snapshot events measurements.
All models,
excepting Options 4
and 5 for I/O boards.
Option 6 for IEC
61850 protocol
November
25th 2005

Table of Contents

Other manuals for GE Multilin F650

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Multilin F650 and is the answer not in the manual?

GE Multilin F650 Specifications

General IconGeneral
BrandGE
ModelMultilin F650
CategoryController
LanguageEnglish

Related product manuals